P200 Pneumatic-to-Current P/I Transducers
Reliable, user-oriented performance


ControlAir's Dahl P200 P/I transducer represents outstanding value in pneumatic to current technology. All solid state circuitry converts standard 3-15, 3-27 or 6-30 psig instrument air into 4-20 or 10-50 mA outputs (4-20 mA only for FM and CSA approval) with uncompromising accuracy and durability. Custom pressure ranges are also available. The P200's explosion-proof housing allows it to stand up to the most hazardous and demanding applications. The P200 is FM approved and CSA certified as NEMA 4 (Enc. 4) for all locations and explosion-proof for Class I, Div. 1, Groups A, B, C, D; dust ignition-proof for Class II, Div. 1, Groups E, F, G; and suitable for Class III, Div. 1 locations.
Specifications
| Inputs
|
Instrument Air:
|
|
Maximum Input |
3 times full scale without recalibration |
|
Outputs |
2 wire: 4-20 mA and 10-50 mA with over-current limit. |
|
Allowable Loads |
700 Ω |
|
Accuracy |
± 0.15% of span guaranteed; ±0.10% of span typical. Includes combined effects of linearity, hysteresis and |
|
Hysteresis |
Negligible |
|
Repeatability |
±0.10% of span max; ±0.03% of span typical |
|
Resolution |
Infinite |
|
Output Ripple |
None |
|
Protection |
N/A |
|
Response Time |
10 m Sec to 99% of step change |
|
Temperature Stability |
Span and Zero: ±0.007% of span per °F maximum deviation from 77°F calibration |
|
Power Supply Stability |
Less than 0.005% of span change in output per volt change at the input terminals |
|
Power Supply |
10 VDC min. to 42 VDC max. at input terminals. Can indefinitely withstand up to 100 VDC without failure |
|
RFI/EMI Effect |
Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter |
|
Operating Temperature Range |
-40°F to 161°F (-40°C to 72°C) |
|
Storage Temperature Range |
-60°F to 161°F (-51°C to 72°C) |
|
Calibration Adjustments |
Multiturn span and zero potentiometers with approximately ±20% of span adjustment range |
|
Loss-of-air Indication |
N/A |
|
Mounting Position Effect |
None |
|
In-process Output Monitoring |
Current: For accurate reading, ammeter must have less than 20 ƒ input resistance on 4-20 mA output (0.40 VDC drop) |
|
Connections |
Signal Air: 1/4" NPT female |
Ordering Information
| Part Number | Description | |||
| P200 | P/I Device, 2-wire, FM explosion-proof, 4-20/10-50 mA* Field selectable |
|||
| *10-50 mA not available with P28 or P30 options | ||||
| P/N | Standard Ranges | P/N | Custom Ranges (psig) Specify range | |
| P11 | 3-15 psig (20-100 kPa) | P50 | 0-.72 to 0-6.0 | |
| P12 | 3-27 psig (20-180 kPa) | P51 | 0-6.0 to 0-18.0 | |
| P13 | 6-30 psig (40-200 kPa) | P52 | 0-18.0 to 0-30.0 | |
| P53 | 0-30.0 to 0.50.0* | |||
| * FM and CSA explosion-proof approvals not applicable above 30 psig | ||||
| Options | P/N | Description | ||
| P21 | Lightening Surge Protector | |||
| P22 | 2” Pipe, “U”-Bolt Hardware | |||
| P23 | Extra 316 SS Tag | |||
| P27* | Internal Meter, NEMA 4 | |||
| P28 | CSA Intrinsically Safe | |||
| P29 | CSA Explosion-proof | |||
| P30 | FM Intrinsically Safe | |||
*Transmitters with P27 option are not FM or CSA approved, explosion-proof
- Part Number = Model + Input Range + Options
- Examples: P200 + P11 + P21
- P290 + P50 (0-5)